mconfigNumTrapReceivers |
.1.3.6.1.4.1.318.2.1.1 |
The number of managers to send traps to.
|
mconfigTrapReceiverEntry |
.1.3.6.1.4.1.318.2.1.2.1 |
The managers to send traps to.
|
mconfigBOOTPEnabled |
.1.3.6.1.4.1.318.2.1.3 |
The value of yes(1) indicates the PowerNet Adapter is configured to
obtain its IP configuration parameters from a BOOTP server.
The value of no(2) indicates adapter will assume IP configuration parameters
values saved in adapter's eeprom, which was orginially configured at local
console.
|
mconfigTFTPServerIP |
.1.3.6.1.4.1.318.2.1.4 |
The IP address of TFTP server. If mconfigBOOTPEnabled is yes(1), then this IP address
is provided by BOOTP server and not allowed to be modified; otherwise, this IP address
can be modified.
Before using TFTP to load new code image, the image file should be placed in proper
directory of the specified TFTP server.
|
newCodeAuthentViaTFTP |
.1.3.6.1.4.1.318.2.1.5 |
Once mcontrolRestartAgent is set to loadAndExecuteNewAgent (3), PowerNet adapter will
start to load the remote image file, for authentication only, instead of saving the code
into flash memory. Only if a validNewAgentCodeImage (1) is found will the agent reboot
the PowerNet adaoter and invoke the loader to load and save new code into the flash memory.
Otherwise, the current agent code will continue to run.
This OID shows the result of the above authentication process.
validNewAgentCodeImage (1) means the code image on TFTP server
is a valid APC agent code and is different version from the current agent.
Once agent identifies this, loader will start to update flash memory with
the new agent code.
sameAgentCodeImage (2) means the code image on TFTP server is exactly the
same as the currently running agent. Currently running agent will not invoke
loader to load the same again.
invalidAgentCodeImage (3) means the code image on TFTP server is NOT a valid
APC agent code. Thus, current agent will not load it into the flash memory.
The value of this OID will be associated with TRAP codeImageAuthentDone.
|
mcontrolRestartAgent |
.1.3.6.1.4.1.318.2.2.1 |
Setting this OID to restartCurrentAgent (1)
will restart the same SNMP agent code currently saved in
flash memory.
Setting this OID to loadAndExecuteNewAgent (3) will enable adapter
to load a new agent code into the flash memory and start to
execute this new agent code. Bootp/tftp is the default protocol.
|
powerNetSoftwareSystemDescription |
.1.3.6.1.4.1.318.1.2.1.1.1 |
A brief description of the PowerNet sub-agent.
|
powerNetSoftwareOid |
.1.3.6.1.4.1.318.1.2.1.1.2 |
The object identifier of the PowerNet sub-agent.
|
powerNetSoftwareSystemUpTime |
.1.3.6.1.4.1.318.1.2.1.1.3 |
The time that the sub-agent has been running.
|
powerNetSoftwareTableSize |
.1.3.6.1.4.1.318.1.2.1.2.1 |
The number of software modules supporting the UPS.
|
powerNetSoftwareEntry |
.1.3.6.1.4.1.318.1.2.1.2.2.1 |
An entry containing information on a software module.
|
upsBasicIdentModel |
.1.3.6.1.4.1.318.1.1.1.1.1.1 |
The UPS model name (e.g. 'APC Smart-UPS 600').
|
upsBasicIdentName |
.1.3.6.1.4.1.318.1.1.1.1.1.2 |
An 8 byte ID string identifying the UPS. This object
can be set by the administrator.
|
upsAdvIdentFirmwareRevision |
.1.3.6.1.4.1.318.1.1.1.1.2.1 |
The firmware revision of the UPS system's microprocessor.
|
upsAdvIdentDateOfManufacture |
.1.3.6.1.4.1.318.1.1.1.1.2.2 |
The date when the UPS was manufactured in mm/dd/yy format.
|
upsAdvIdentSerialNumber |
.1.3.6.1.4.1.318.1.1.1.1.2.3 |
An 8-character string identifying the serial number of
the UPS internal microprocessor. This number is set at
the factory. NOTE: This number does NOT correspond to
the serial number on the rear of the UPS.
|
upsBasicBatteryStatus |
.1.3.6.1.4.1.318.1.1.1.2.1.1 |
The status of the UPS batteries. A batteryLow(3)
value indicates the UPS will be unable to sustain the
current load, and its services will be lost if power is
not restored. The amount of run time in reserve at the
time of low battery can be configured by the
upsAdvConfigLowBatteryRunTime.
|
upsBasicBatteryTimeOnBattery |
.1.3.6.1.4.1.318.1.1.1.2.1.2 |
The elapsed time since the UPS has switched to battery
power.
|
upsBasicBatteryLastReplaceDate |
.1.3.6.1.4.1.318.1.1.1.2.1.3 |
The date when the UPS system's batteries were last replaced
in mm/dd/yy format. For Smart-UPS models, this value
is originally set in the factory. When the UPS batteries
are replaced, this value should be reset by the administrator.
|
upsAdvBatteryCapacity |
.1.3.6.1.4.1.318.1.1.1.2.2.1 |
The remaining battery capacity expressed in
percent of full capacity.
|
upsAdvBatteryTemperature |
.1.3.6.1.4.1.318.1.1.1.2.2.2 |
The current internal UPS temperature expressed in
Celsius.
|
upsAdvBatteryRunTimeRemaining |
.1.3.6.1.4.1.318.1.1.1.2.2.3 |
The UPS battery run time remaining before battery
exhaustion.
|
upsAdvBatteryReplaceIndicator |
.1.3.6.1.4.1.318.1.1.1.2.2.4 |
Indicates whether the UPS batteries need replacing.
|
upsAdvBatteryNumOfBattPacks |
.1.3.6.1.4.1.318.1.1.1.2.2.5 |
The number of external battery packs connected to the UPS. If
the UPS does not use smart cells then the agent reports
ERROR_NO_SUCH_NAME.
|
upsAdvBatteryNumOfBadBattPacks |
.1.3.6.1.4.1.318.1.1.1.2.2.6 |
The number of external battery packs connected to the UPS that
are defective. If the UPS does not use smart cells then the
agent reports ERROR_NO_SUCH_NAME.
|
upsBasicInputPhase |
.1.3.6.1.4.1.318.1.1.1.3.1.1 |
The current AC input phase.
|
upsAdvInputLineVoltage |
.1.3.6.1.4.1.318.1.1.1.3.2.1 |
The current utility line voltage in VAC.
|
upsAdvInputMaxLineVoltage |
.1.3.6.1.4.1.318.1.1.1.3.2.2 |
The maximum utility line voltage in VAC over the
previous 1 minute period.
|
upsAdvInputMinLineVoltage |
.1.3.6.1.4.1.318.1.1.1.3.2.3 |
The minimum utility line voltage in VAC over the
previous 1 minute period.
|
upsAdvInputFrequency |
.1.3.6.1.4.1.318.1.1.1.3.2.4 |
The current input frequency to the UPS system in Hz.
|
upsAdvInputLineFailCause |
.1.3.6.1.4.1.318.1.1.1.3.2.5 |
The reason for the occurrence of the last transfer to UPS
battery power. The variable is set to:
- noTransfer(1) -- if there is no transfer yet.
- highLineVoltage(2) -- if the transfer to battery is caused
by an over voltage greater than the high transfer vloltage.
- brownout(3) -- if the duration of the outage is greater than
five seconds and the line voltage is between 40% of the
rated output voltage and the low transfer voltage.
- blackout(4) -- if the duration of the outage is greater than five
seconds and the line voltage is between 40% of the rated
output voltage and ground.
- smallMomentarySag(5) -- if the duration of the outage is less
than five seconds and the line voltage is between 40% of the
rated output voltage and the low transfer voltage.
- deepMomentarySag(6) -- if the duration of the outage is less
than five seconds and the line voltage is between 40% of the
rated output voltage and ground. The variable is set to
- smallMomentarySpike(7) -- if the line failure is caused by a
rate of change of input voltage less than ten volts per cycle.
- largeMomentarySpike(8) -- if the line failure is caused by
a rate of change of input voltage greater than ten volts per cycle.
|
upsBasicOutputStatus |
.1.3.6.1.4.1.318.1.1.1.4.1.1 |
The current state of the UPS. If the UPS is unable
to determine the state of the UPS this variable is set
to unknown(1).
|
upsBasicOutputPhase |
.1.3.6.1.4.1.318.1.1.1.4.1.2 |
The current output phase.
|
upsAdvOutputVoltage |
.1.3.6.1.4.1.318.1.1.1.4.2.1 |
The output voltage of the UPS system in VAC.
|
upsAdvOutputFrequency |
.1.3.6.1.4.1.318.1.1.1.4.2.2 |
The current output frequency of the UPS system in Hz.
|
upsAdvOutputLoad |
.1.3.6.1.4.1.318.1.1.1.4.2.3 |
The current UPS load expressed in percent
of rated capacity.
|
upsAdvOutputCurrent |
.1.3.6.1.4.1.318.1.1.1.4.2.4 |
The current in ampres drawn by the load on the UPS.
|
upsBasicConfigNumDevices |
.1.3.6.1.4.1.318.1.1.1.5.1.1 |
The number of devices that are plugged into the UPS.
|
upsBasicConfigDeviceEntry |
.1.3.6.1.4.1.318.1.1.1.5.1.2.1 |
The devices plugged in to the UPS.
|
upsAdvConfigRatedOutputVoltage |
.1.3.6.1.4.1.318.1.1.1.5.2.1 |
The nominal output voltage from the UPS in VAC.
Possible values are 100, 120, 208, 220, 225, 230 and 240.
NOTE: Only units that are 220, 225, 230 and 240 can be
changed. Allowable set values are 220, 225, 230, and 240.
For these adjustable units, if a value other than
a supported value is provided in a set request, the
UPS interprets it as the next lower acceptable value.
If the provided value is lower than the lowest acceptable
value, the lowest acceptable value is used.
|
upsAdvConfigHighTransferVolt |
.1.3.6.1.4.1.318.1.1.1.5.2.2 |
The maximum line voltage in VAC allowed before the
UPS system transfers to battery backup.
Allowed values depend on the UPS used:
100 volt units allow settings of 108, 110, 112, and 114.
120 volt units allow settings of 129, 132, 135, and 138.
208 volt units allow settings of 224, 229, 234, and 239.
230 volt units allow settings of 253, 264, 271, and 280.
Matrix Notes:
Matrix units configured for 208V input allow settings of
240, 244, 248, and 252. Matrix units configured for 240V
input allow settings of 276, 264, 253, and 282.
If a value other than a supported value is provided in a
set request, the UPS interprets it as the next lower
acceptable value. If the provided value is lower than
the lowest acceptable value, the lowest acceptable
value is used.
|
upsAdvConfigLowTransferVolt |
.1.3.6.1.4.1.318.1.1.1.5.2.3 |
The minimum line voltage in VAC allowed before the
UPS system transfers to battery backup.
Allowable values depend on the UPS used:
100 volt units allow settings of 81, 83, 85, 87.
120 volt units allow settings of 97, 100, 103, 106.
208 volt units allow settings of 168, 172, 177, 182.
230 volt units allow settings of 188, 196, 204, 208.
Matrix Notes:
Matrix units configured for 208V input have a fixed low
transfer voltage of 156 volts.
Matrix units configured for 240V input have a fixed low
transfer voltage of 180 volts.
If a value other than a supported value is provided in a
set request, the UPS interprets it as a the next higher
acceptable value. If the provided value is higher than
the highest acceptable value, the highest acceptable
value is used.
|
upsAdvConfigAlarm |
.1.3.6.1.4.1.318.1.1.1.5.2.4 |
A flag indicating how the UPS should handle audible
line fail alarms.
|
upsAdvConfigAlarmTimer |
.1.3.6.1.4.1.318.1.1.1.5.2.5 |
The time after initial line failure at which the UPS
begins emitting audible alarms (beeping). This timer is
observerd only if the value of extControlAlarm is timed(2).
Allowed values are 0 or 30 seconds.
If a value other than a supported value is provided in a
set request, the UPS interprets it as a the next lower
acceptable value. If the provided value is lower than
the lowest acceptable value, the lowest acceptable
value is used.
|
upsAdvConfigMinReturnCapacity |
.1.3.6.1.4.1.318.1.1.1.5.2.6 |
The minimum battery capacity required before the UPS will
return from a low battery shutdown condition. The capacity is
measured from 0% battery capacity (or Low Battery) as a percent
of full capacity (100%). In other words, the UPS will not re-energize
the output until the battery has charged so that its' capacity is equal
to this value. Allowed values are 0, 10, 25, or 90 percent.
If a value other than a supported value is provided in a
set request, the UPS interprets the value as the next higher
acceptable value. If the provided value is higher than
the highest acceptable value, the highest acceptable
value (90%) is used.
|
upsAdvConfigSensitivity |
.1.3.6.1.4.1.318.1.1.1.5.2.7 |
The sensitivity of the UPS to utility line abnormalities
or noises.
|
upsAdvConfigLowBatteryRunTime |
.1.3.6.1.4.1.318.1.1.1.5.2.8 |
The desired run time of the UPS, in seconds, once the
low battery condition is reached. Allowed values are 120,
300, 420, or 600 seconds. During this time the UPS will
produce a constant warning tone which can not be disabled.
If a value other than a supported value is provided in a set
request, the UPS interprets the value as the next higher
acceptable value. If the provided value is higher than the
highest acceptable value, the highest acceptable value is used.
|
upsAdvConfigReturnDelay |
.1.3.6.1.4.1.318.1.1.1.5.2.9 |
The delay in seconds after utility line power returns
before the UPS will turn on. This value is also used
when the UPS comes out of a reboot and before the UPS
wakes up from 'sleep' mode. Allowed values are 0, 60,
180 and 300 seconds.
If a value other than a supported value is provided in a
set request, the UPS interprets it as a the next higher
acceptable value. If the provided value is higher than
the highest acceptable value, the highest acceptable
value is used.
|
upsAdvConfigShutoffDelay |
.1.3.6.1.4.1.318.1.1.1.5.2.10 |
The delay in seconds the UPS remains on after being told
to turn off. Allowed values are 20, 180, 300, and
600 seconds.
If a value other than a supported value is provided in a
set request, the UPS interprets it as a the next higher
acceptable value. If the provided value is higher than
the highest acceptable value, the highest acceptable
value is used.
|
upsAdvConfigUpsSleepTime |
.1.3.6.1.4.1.318.1.1.1.5.2.11 |
The time in seconds for the UPS to go to 'sleep' when
instructed. When in sleep mode, the UPS will not provide
output power regardless of the input line state. Once the
specified time has elapsed, output power will be restored.
This is a configuration setting. The UPS will not go to
sleep until told to do so by the manager from a management
station.
Any input value is allowed, however the UPS only recognizes
1/10 of an hour increments. The provided value will be
rounded to the closest 1/10 of an hour with one exception:
Any value entered between 1 and 540 seconds will be rounded
to 360 seconds (or 6 minutes).
|
upsAdvConfigSetEEPROMDefaults |
.1.3.6.1.4.1.318.1.1.1.5.2.12 |
WRITE: Resets the UPS EEPROM variables to default values.
READ: returns 0
|
upsAdvConfigDipSwitchEntry |
.1.3.6.1.4.1.318.1.1.1.5.2.13.1 |
The current setting of one dip switch.
|
upsAdvConfigBattExhaustThresh |
.1.3.6.1.4.1.318.1.1.1.5.2.14 |
The number of seconds prior to battery exhaustion when the
UPS will switch off power to it's load.
|
upsAdvConfigPassword |
.1.3.6.1.4.1.318.1.1.1.5.2.15 |
The password entered at the UPS front panel to enable local
configuation of the EEProm. If the password is disabled or
is not supported, then the agent returns a null string.
|
apcUpsConfigEntry |
.1.3.6.1.4.1.318.1.1.1.5.2.16.1 |
The table entry for a configurable UPS variable.
|
upsBasicControlConserveBattery |
.1.3.6.1.4.1.318.1.1.1.6.1.1 |
Setting this variable to turnUpsOffToConserveBattery(2)
causes a UPS on battery to be put into 'sleep' mode. The
UPS will turn back on when utility power is restored.
Attempting to turn off a UPS that is not on battery will
result in a badValue error.
Setting this value to noTurnOffUps(1) has no
effect.
The value noTurnOffUps(1) will always be returned
when the variable is read.
|
upsAdvControlUpsOff |
.1.3.6.1.4.1.318.1.1.1.6.2.1 |
Setting this variable to turnUpsOff(2) causes
the UPS to shut off. When in this state, the UPS
will not provide output power regardless of the input
line state. The ON/OFF switch on the UPS
must be toggled for the UPS to return to operation.
Setting this value to noTurnUpsOff(1) has no
effect.
The value noTurnUpsOff(1) will always be returned
when the variable is read.
|
upsAdvControlRebootUps |
.1.3.6.1.4.1.318.1.1.1.6.2.2 |
Setting this variable to rebootUps(2) causes the
UPS to shut off and turn back on.
Setting this value to noRebootUps(1) has no effect.
The value noRebootUps(1) will always be returned
when the variable is read.
|
upsAdvControlUpsSleep |
.1.3.6.1.4.1.318.1.1.1.6.2.3 |
Setting this variable to putUpsToSleep(2) causes
the UPS to go to sleep for the time specified by
upsAdvConfigUpsSleepTime.
When in sleep mode, the UPS will not provide output
power regardless of the input line state. Once the
specified time has elapsed, output power will be
restored.
Setting this value to noPutUpsToSleep(1) has no
effect.
The value noPutUpsToSleep(1) will always be returned
when the variable is read.
|
upsAdvControlSimulatePowerFail |
.1.3.6.1.4.1.318.1.1.1.6.2.4 |
Setting this variable to simulatePowerFailure(2) causes
the UPS switch to battery power.
Setting this value to noSimulatePowerFailure(1) has no
effect.
The value noSimulatePowerFailure(1) will always be returned
when the variable is read.
|
upsAdvControlFlashAndBeep |
.1.3.6.1.4.1.318.1.1.1.6.2.5 |
Setting this variable to flashAndBeep(2) causes the
UPS to beep and simultaneously turn on the UPS front
panel lights (Smart-UPS only).
Setting this value to noFlashAndBeep(1) has no
effect.
The value noFlashAndBeep(1) will always be returned
when the variable is read.
|
upsAdvControlTurnOnUPS |
.1.3.6.1.4.1.318.1.1.1.6.2.6 |
Setting this variable to turnOnUPS(2) causes the
UPS to be turned on immediately, provided
upsBasicOutputStatus does not read ON.
Setting this value to noTurnOnUPS(1) has no
effect.
The value noTurnOnUPS(1) will always be returned
when the variable is read.
This action is only available with the APC
Mini-SNMP Adapter.
|
upsAdvControlBypassSwitch |
.1.3.6.1.4.1.318.1.1.1.6.2.7 |
This switch pertains to the Matrix UPS. It switchs the
UPS in or out of bypass mode.
|
upsAdvTestDiagnosticSchedule |
.1.3.6.1.4.1.318.1.1.1.7.2.1 |
The UPS system's automatic battery test schedule.
|
upsAdvTestDiagnostics |
.1.3.6.1.4.1.318.1.1.1.7.2.2 |
Setting this variable to testDiagnostics(2) causes
the UPS to perform a diagnostic self test.
Setting this value to noTestDiagnostics(1) has no
effect.
The value noTestDiagnostics(1) will always be returned
when the variable is read.
|
upsAdvTestDiagnosticsResults |
.1.3.6.1.4.1.318.1.1.1.7.2.3 |
The results of the last UPS diagnostics test performed.
|
upsAdvTestLastDiagnosticsDate |
.1.3.6.1.4.1.318.1.1.1.7.2.4 |
The date the last UPS diagnostics test was performed in
mm/dd/yy format.
|
upsAdvTestRuntimeCalibration |
.1.3.6.1.4.1.318.1.1.1.7.2.5 |
Setting this variable to performCalibration(2) causes
the UPS to discharge to calibrate the UPS.
The test will only start if the battery capacity is 100%.
The test runs until capacity is less than 25%.
Setting this variable to cancelCurrentCalibration(3)
after setting performCalibration(2) will cancel the
current discharge.
Setting this variable to noPerformCalibration(1)
will have no effect.
The value noPerformCalibration(1) will always be returned
when the variable is read.
The result of the calibration will be saved in
upsAdvTestCalibrationResult.
|
upsAdvTestCalibrationResults |
.1.3.6.1.4.1.318.1.1.1.7.2.6 |
The results of the last runtime calibration.
Value ok(1) means a successful runtime calibration.
Value invalidCalibration(2) indicates last calibration did
not take place since the battery capacity was below
100%.
Value calibrationInProgress(3) means a calibration
is occurring now.
|
upsAdvTestCalibrationDate |
.1.3.6.1.4.1.318.1.1.1.7.2.7 |
The date the last UPS runtime calibration was
performed in mm/dd/yy format.
|
upsCommStatus |
.1.3.6.1.4.1.318.1.1.1.8.1 |
The status of agent's communication with UPS.
|
mUpsEnvironAmbientTemperature |
.1.3.6.1.4.1.318.1.1.2.1.1 |
The ambient temperature in Celsius.
|
mUpsEnvironRelativeHumidity |
.1.3.6.1.4.1.318.1.1.2.1.2 |
The relative humidity as a percentage.
|
mUpsContactNumContacts |
.1.3.6.1.4.1.318.1.1.2.2.1 |
The number of contacts supported by the Measure-UPS.
|
mUpsContactEntry |
.1.3.6.1.4.1.318.1.1.2.2.2.1 |
A contact entry containing information for a given contact.
|
serialPort2Mode |
.1.3.6.1.4.1.318.1.1.3.1.2.1.1 |
Setting this variable to passthrough will enable mini's port2
behave like a UPS port. Choosing localConsole will enable the port
to be used as local console.
|
setPulseOnTXD |
.1.3.6.1.4.1.318.1.1.3.1.2.2.1 |
Setting this variable to setPulseOnTXD(2)
causes adapter to generate a PULSE on TXD pin of serial port 2.
The duration in the prototype implementation will be 1 second.
Setting this value to noSetPulseOnTXD(1) has no
effect.
The value noSetPulseOnTXD(1) will always be returned
when the variable is read.
Setting this value to setTXDLow(3), or setTXDHigh(4) will keep TXD
always low or high respectively.
|
communicationLost |
1 |
SEVERE: Communication to the UPS has been lost. Steps
to reestablish communication are in progress.
|
upsOverload |
2 |
SEVERE: The UPS has sensed a load greater than 100 percent
of its rated capacity.
|
upsDiagnosticsFailed |
3 |
SEVERE: The UPS failed its internal diagnostic self-test.
|
upsDischarged |
4 |
SEVERE: The UPS batteries are discharged; if utility power fails
an immediate low battery condition will exist. Sufficient runtime
for necessary action cannot be guaranteed.
|
upsOnBattery |
5 |
WARNING: The UPS has switched to battery backup power.
|
smartBoostOn |
6 |
WARNING: The UPS has enabled SmartBoost.
|
lowBattery |
7 |
SEVERE: The UPS batteries are low and will soon be exhausted.
If utility power is not restored the UPS will put itself
to 'sleep' and immediately cut power to the load.
|
communicationEstablished |
8 |
INFORMATION: Communication with the UPS has been established.
|
powerRestored |
9 |
INFORMATION: Utility power has been restored.
|
upsDiagnosticsPassed |
10 |
INFORMATION: The UPS passed its internal self-test.
|
returnFromLowBattery |
11 |
INFORMATION: The UPS has returned from a low battery
condition.
|
upsTurnedOff |
12 |
WARNING: The UPS has been turned 'off' by the management station.
|
upsSleeping |
13 |
WARNING: The UPS is entering 'sleep' mode. Power
to the load will be cut off.
|
upsWokeUp |
14 |
INFORMATION: The UPS has returned from 'sleep' mode. Power
to the load has been restored.
|
upsRebootStarted |
15 |
WARNING: The UPS has started its reboot sequence.
The UPS will reboot itself at this time.
|
upsDipSwitchChanged |
16 |
WARNING: The dip switch settings on the UPS have been
changed, possibly altering UPS performance.
|
upsBatteryNeedsReplacement |
17 |
SEVERE: The batteries of the UPS need immediate replacement.
|
contactFault |
18 |
SEVERE: One of the contacts on the Measure-UPS has
changed from its default position.
|
contactFaultResolved |
19 |
INFORMATION: A fault on one of the Measure-UPS contacts
has been resolved.
|
hardwareFailureBypass |
20 |
SEVERE: UPS on bypass due to hardware failure
|
softwareBypass |
21 |
WARNING: UPS on bypass - user set via software or panel
|
switchedBypass |
22 |
WARNING: UPS on bypass - user set via rear switch
|
returnFromBypass |
23 |
INFORMATIONAL: UPS has returned from bypass
|
bypassPowerSupplyFailure |
24 |
SEVERE: Base module bypass power supply needs repair
|
baseFanFailure |
25 |
SEVERE: Base module fan needs repair
|
batteryPackCommLost |
26 |
SEVERE: Check installation of external battery packs signal cable
|
batteryPackCommEstablished |
27 |
INFORMATIONAL: UPS is communicating with the external battery packs.
|
calibrationStart |
28 |
INFORMATIONAL: A battery calibration test has been initiated on the UPS.
|
restartAgent |
29 |
INFORMATIONAL: Agent restarting as commanded by manager.
|
upsTurnedOn |
30 |
INFORMATIONAL: A UPS is turned on.
|
smartAvrReducing |
31 |
WARNING: The UPS is reducing the line voltage via Smart-AVR.
|
codeAuthenticationDone |
32 |
INFORMATIONAL: Authentication on agent code image is done.
|