ActiveXperts Network Monitor 2019##AdminFavorites

UPS2-MIB by vendor Enterasys Networks Inc

UPS2-MIB file content

The SNMP protocol is used to for conveying information and commands between agents and managing entities. SNMP uses the User Datagram Protocol (UDP) as the transport protocol for passing data between managers and agents. The reasons for using UDP for SNMP are, firstly it has low overheads in comparison to TCP, which uses a 3-way hand shake for connection. Secondly, in congested networks, SNMP over TCP is a bad idea because TCP in order to maintain reliability will flood the network with retransmissions.

Management information (MIB) is represented as a collection of managed objects. These objects together form a virtual information base called MIB. An agent may implement many MIBs, but all agents must implement a particular MIB called MIB-II [16]. This standard defines variables for things such as interface statistics (interface speeds, MTU, octets sent, octets received, etc.) as well as various other things pertaining to the system itself (system location, system contact, etc.). The main goal of MIB-II is to provide general TCP/IP management information.

Use ActiveXperts Network Monitor 2019 to import vendor-specific MIB files, inclusing UPS2-MIB.


Vendor: Enterasys Networks Inc
Mib: UPS2-MIB  [download]  [view objects]
Tool: ActiveXperts Network Monitor 2019 [download]    (ships with advanced SNMP/MIB tools)
UPS2-MIB DEFINITIONS ::= BEGIN

        --  ctron-ups2-mib.txt  The UPS Revision 2 MIB
        --  Revision: 1.01.00
        --  Part Number:  
        --  Date: September 12, 1995

        --  Cabletron Systems, Inc.
        --  35 Industrial Way, P.O. Box 5005
        --  Rochester, NH 03867-0505
        --  (603) 332-9400
        --  support@ctron.com

        --  This module provides authoritative definitions for Cabletron's
        --  enterprise-specific UPS MIB.
        --
        --  This module will be extended, as needed.
        --

        --  Cabletron Systems reserves the right to make changes in 
        --  specification and other information contained in this document 
        --  without prior notice.  The reader should consult Cabletron Systems
        --  to determine whether any such changes have been made.
        --
        --  In no event shall Cabletron Systems be liable for any incidental, 
        --  indirect, special, or consequential damages whatsoever (including 
        --  but not limited to lost profits) arising out of or related to this
        --  document or the information contained in it, even if Cabletron
        --  Systems has been advised of, known, or should have known, the 
        --  possibility of such damages.
        --
        --  Cabletron grants vendors, end-users, and other interested parties
        --  a non-exclusive license to use this Specification in connection
        --  with the management of Cabletron products.

        --  Copyright August 95 Cabletron Systems

        IMPORTS
                ctUPS
                        FROM CTRON-MIB-NAMES
                DisplayString
                        FROM RFC1213-MIB
                OBJECT-TYPE
                        FROM RFC-1212;

        --  Textual convention


        --  DisplayString ::= OCTET STRING
        --  This data type is used to model textual information taken from
        --  the NVT ASCII character set.  By convention, objects with this
        --  syntax, unless explicitly stated, are declared as having:
        --
        --  SIZE (0..255)


        --===============    group definitions     ====================

        upsSystem               OBJECT IDENTIFIER  ::= { ctUPS 1 }
        upsId                   OBJECT IDENTIFIER  ::= { ctUPS 2 }
        upsBattery              OBJECT IDENTIFIER  ::= { ctUPS 3 }
        upsInput                OBJECT IDENTIFIER  ::= { ctUPS 4 }
        upsOutput               OBJECT IDENTIFIER  ::= { ctUPS 5 }
        upsStatus               OBJECT IDENTIFIER  ::= { ctUPS 6 }
        upsConfig               OBJECT IDENTIFIER  ::= { ctUPS 7 }
        upsExtMeas              OBJECT IDENTIFIER  ::= { ctUPS 8 }
        upsAddlFuncs            OBJECT IDENTIFIER  ::= { ctUPS 9 }



        --================    upsSystem group      ====================

        --  UPS System Group
        --  Implementation of this group is mandatory
        --  This group covers system-level information on the UPSs available

        upsNumUPSs  OBJECT-TYPE
            SYNTAX  INTEGER (0..2)
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "The number of UPSs available."
            ::= { upsSystem 1 }



        --===============    upsId group          =====================

        --  UPS Identification Group
        --  Implementation of this group is mandatory if one or more UPSs
        --  are to be monitored
        --  This group covers identification information on the UPSs available

        upsIdTable  OBJECT-TYPE
            SYNTAX  SEQUENCE OF UpsIdEntry
            ACCESS  not-accessible
            STATUS  mandatory
            DESCRIPTION
                "A list of identification table entries.  The number of
                 entries is given by the value of upsNumUPSs."
            ::= { upsId 1 }

        upsIdEntry  OBJECT-TYPE
            SYNTAX  UpsIdEntry
            ACCESS  not-accessible
            STATUS  mandatory
            DESCRIPTION
                "An entry containing objects for a particular UPS."
            INDEX  { upsIndex }
            ::= { upsIdTable 1 }

        UpsIdEntry  ::=
            SEQUENCE {
                upsIndex
                    INTEGER,
                upsName
                    DisplayString,
                upsModelType
                    INTEGER,
                upsFwVersion
                    DisplayString,
                upsSerialNumber
                    DisplayString,
                upsManufDate
                    DisplayString
            }

        upsIndex  OBJECT-TYPE
            SYNTAX  INTEGER
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "A unique value which identifies a particular UPS."
            ::= { upsIdEntry 1 }

        upsName  OBJECT-TYPE
            SYNTAX  DisplayString (SIZE(0..8))
            ACCESS  read-write
            STATUS  mandatory
            DESCRIPTION
                "The UPS's name.  A maximum of 8 characters may be specified.
                 This object is initialized to the UPS's model name."
            ::= { upsIdEntry 2 }

        upsModelType  OBJECT-TYPE
            SYNTAX  INTEGER {
                        smartUps250(1),
                        smartUps400(2),
                        smartUps600(3),
                        smartUps900(4),
                        smartUps1250(5),
                        smartUps2000(6),
                        matrixUps3000(7),
                        matrixUps5000(8),
                        other(9)
                }
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "The UPS's base model type."
            ::= { upsIdEntry 3 }

        upsFwVersion    OBJECT-TYPE
            SYNTAX  DisplayString (SIZE(0..8))
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "The UPS's firmware version."
            ::= { upsIdEntry 4 }

        upsSerialNumber OBJECT-TYPE
            SYNTAX  DisplayString (SIZE(0..16))
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "The UPS's serial number as set at the factory."
            ::= { upsIdEntry 5 }

        upsManufDate    OBJECT-TYPE
            SYNTAX  DisplayString (SIZE(0..8))
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "The UPS's date of manufacture in the format mm/dd/yy."
            ::= { upsIdEntry 6 }



        --===============    upsBattery group          ====================

        --  UPS Battery Group
        --  Implementation of this group is mandatory if one or more UPSs
        --  are to be monitored
        --  This group covers information on the Batteries within each UPS 


        upsBatteryTable  OBJECT-TYPE
            SYNTAX  SEQUENCE OF UpsBatteryEntry
            ACCESS  not-accessible
            STATUS  mandatory
            DESCRIPTION
                "A list of battery table entries.  The number of
                 entries is given by the value of upsNumUPSs."
            ::= { upsBattery 1 }

        upsBatteryEntry  OBJECT-TYPE
            SYNTAX  UpsBatteryEntry
            ACCESS  not-accessible
            STATUS  mandatory
            DESCRIPTION
                "An entry containing objects for a particular UPS."
            INDEX  { upsIndex }
            ::= { upsBatteryTable 1 }

        UpsBatteryEntry  ::=
            SEQUENCE {
                upsBatteryCapacity 
                    INTEGER,
                upsBatteryVoltage 
                    INTEGER,
                upsBatteryTest
                    INTEGER,
                upsBatteryTestResult
                    INTEGER,
                upsRunTimeCalibration
                    INTEGER,
                upsEstimatedRunTimeRemaining
                    INTEGER,
                upsTransferCause
                    INTEGER,
                upsBatteryTestTime 
                    INTEGER,
                upsLowBatteryWarning
                    INTEGER
            }

        upsBatteryCapacity  OBJECT-TYPE
            SYNTAX  INTEGER
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "The UPS's remaining battery capacity expressed as a percent
                 of the fully charged condition.  The value of this object is
                 the actual percentage * 10 (that is, to determine the actual
                 percentage, divide the value of this object by 10)."
            ::= { upsBatteryEntry 1 }

        upsBatteryVoltage  OBJECT-TYPE
            SYNTAX  INTEGER
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "The UPS's present battery voltage.  The value of this object
                 is the actual voltage * 100 (that is, to determine the actual
                 voltage, divide the value of this object by 100)."
            ::= { upsBatteryEntry 2 }

        upsBatteryTest  OBJECT-TYPE
            SYNTAX  INTEGER {
                        initiateTest(1)
                }
            ACCESS  read-write
            STATUS  mandatory
            DESCRIPTION
                "This object may be written to initiate testing of the UPS's
                 battery packs.  Reading this object will always return a 0."
            ::= { upsBatteryEntry 3 }

        upsBatteryTestResult  OBJECT-TYPE
            SYNTAX  INTEGER {
                        batteryOK(1),
                        batteryBad(2),
                        noRecentTest(3),
                        invalidTestDueToOverload(4)
                }
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                 "The result of the last battery test performed."
            ::= { upsBatteryEntry 4 }

        upsRunTimeCalibration  OBJECT-TYPE
            SYNTAX  INTEGER {
                        performTest(1),
                        abortTest(2),
                        testInProgress(3),
                        testNotInProgress(4)
                }
            ACCESS  read-write
            STATUS  mandatory
            DESCRIPTION
                "This object may be written to initiate or terminate the test
                 used to calibrate the returned run time value.  This test
                 will only run if battery capacity is 100%.  Results of this 
                 test can be retrieved by upsEstimatedRunTimeRemaining.  Valid
                 values for writing are 1 (initiate test) and 2 (terminate test).
                 In addition, this object may be read to determine whether
                 the test is currently running.  Valid values for reading
                 are 3 (test is in progress) and 4 (test is not in progress)."
            ::= { upsBatteryEntry 5 }

        upsEstimatedRunTimeRemaining  OBJECT-TYPE
            SYNTAX  INTEGER 
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "The UPS's estimated remaining run time in minutes.  The UPS
                 may be queried when operating in the on-line, bypass, or
                 on-battery modes of operation.  The run time estimate is
                 based on available battery capacity and output load."
            ::= { upsBatteryEntry 6 }

        upsTransferCause  OBJECT-TYPE
            SYNTAX  INTEGER {
                        noTransfer(1),
                        selfTest(2),
                        inputLineSpike(3),
                        inputLowVoltage(4),
                        inputHighVoltage(5),
                        inputLineFrequencyBad(6)
                }
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "The reason for the most recent transfer to on-battery 
                 operation."
            ::= { upsBatteryEntry 7 }

        upsBatteryTestTime  OBJECT-TYPE
            SYNTAX  INTEGER {
                        twoWeeks(1),
                        oneWeek(2),
                        startupOnly(3),
                        off(4)
                }
            ACCESS  read-write
            STATUS  mandatory
            DESCRIPTION
                "The frequency of execution of the UPS's automatic battery
                 test.  The test may be run immediately upon startup, upon
                 startup and every 7 days thereafter, upon startup and every
                 14 days thereafter, or never."
            DEFVAL { twoWeeks }
            ::= { upsBatteryEntry 8 }

        upsLowBatteryWarning  OBJECT-TYPE
            SYNTAX  INTEGER {
                        twoMinutes(1),
                        fiveMinutes(2),
                        sevenMinutes(3),
                        tenMinutes(4)
                }
            ACCESS  read-write
            STATUS  mandatory
            DESCRIPTION
                "The interval between activation of the UPS's low battery
                 alarm warnings and shutdown of the UPS."
            DEFVAL { twoMinutes }
            ::= { upsBatteryEntry 9 }


        --===============    upsInput group          ====================

        --  UPS Input Group
        --  Implementation of this group is mandatory if one or more UPSs
        --  are to be monitored
        --  This group covers information on the AC Inputs to each UPS 

        upsInputTable  OBJECT-TYPE
            SYNTAX  SEQUENCE OF UpsInputEntry
            ACCESS  not-accessible
            STATUS  mandatory
            DESCRIPTION
                "A list of input table entries.  The number of
                 entries is given by the value of upsNumUPSs."
            ::= { upsInput 1 }

        upsInputEntry  OBJECT-TYPE
            SYNTAX  UpsInputEntry
            ACCESS  not-accessible
            STATUS  mandatory
            DESCRIPTION
                "An entry containing objects for a particular UPS."
            INDEX  { upsIndex }
            ::= { upsInputTable 1 }

        UpsInputEntry  ::=
            SEQUENCE {
                upsInputUtilityVoltage  
                    INTEGER,
                upsInputVoltage  
                    INTEGER,
                upsInputFailureSensitivity  
                    INTEGER,
                upsInputMaxVoltage  
                    INTEGER,
                upsInputMinVoltage  
                    INTEGER,
                upsInputFrequency 
                    INTEGER
            }

        upsInputUtilityVoltage  OBJECT-TYPE
            SYNTAX  INTEGER {
                        vac100(1),
                        vac120(2),
                        vac208(3),
                        vac220(4)               -- 220/230/240
                }
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "The UPS's utility voltage version."
            ::= { upsInputEntry 1 }

        upsInputVoltage  OBJECT-TYPE
            SYNTAX  INTEGER
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "The UPS's measured utility input voltage.  The value
                 of this object is the actual voltage * 10 (that is, to
                 determine the actual voltage, divide the value of this
                 object by 10)."
            ::= { upsInputEntry 2 }

        upsInputFailureSensitivity  OBJECT-TYPE
            SYNTAX  INTEGER {
                        high(1),
                        medium(2),
                        low(3),
                        auto(4)
                }
            ACCESS  read-write
            STATUS  mandatory
            DESCRIPTION
                "The sensitivity of the UPS to rapid changes in utility
                 voltage (e.g., blackouts, spikes, or notches) or
                 abnormal changes in utility frequency."
            DEFVAL { high }
            ::= { upsInputEntry 3 }

        upsInputMaxVoltage  OBJECT-TYPE
            SYNTAX  INTEGER
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "The UPS's maximum input voltage recorded since this object 
                 was last read.  The value of this object is the actual 
                 voltage * 10 (that is, to determine the actual voltage,
                 divide the value of this object by 10)."
            ::= { upsInputEntry 4 }

        upsInputMinVoltage  OBJECT-TYPE
            SYNTAX  INTEGER
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "The UPS's minimum input voltage recorded since this object 
                 was last read.  The value of this object is the actual 
                 voltage * 10 (that is, to determine the actual voltage,
                 divide the value of this object by 10)."
            ::= { upsInputEntry 5 }

        upsInputFrequency  OBJECT-TYPE
            SYNTAX  INTEGER
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "The UPS's present internal operating frequency in Hz.
                 The value of this object is the actual frequency * 100
                 (that is, to determine the actual frequency, divide
                 the value of this object by 100)."
            ::= { upsInputEntry 6 }


        --===============    upsOutput group          ===================

        --  UPS Output Group
        --  Implementation of this group is mandatory if one or more UPSs
        --  are to be monitored
        --  This group covers information on the AC Outputs from each UPS 

        upsOutputTable  OBJECT-TYPE
            SYNTAX  SEQUENCE OF UpsOutputEntry
            ACCESS  not-accessible
            STATUS  mandatory
            DESCRIPTION
                "A list of output table entries.  The number of
                 entries is given by the value of upsNumUPSs."
            ::= { upsOutput 1 }

        upsOutputEntry  OBJECT-TYPE
            SYNTAX  UpsOutputEntry
            ACCESS  not-accessible
            STATUS  mandatory
            DESCRIPTION
                "An entry containing objects for a particular UPS."
            INDEX  { upsIndex }
            ::= { upsOutputTable 1 }

        UpsOutputEntry  ::=
            SEQUENCE {
                upsOutputVoltage
                    INTEGER,
                upsOutputUtilityVoltage 
                    INTEGER,
                upsOutputPower  
                    INTEGER
            }

        upsOutputVoltage  OBJECT-TYPE
            SYNTAX  INTEGER
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "The measured UPS output voltage.  The value of this
                 object is the actual voltage * 10 (that is, to determine
                 the actual voltage, divide the value of this object by
                 10)."
            ::= { upsOutputEntry 1 }

        upsOutputUtilityVoltage  OBJECT-TYPE
            SYNTAX  INTEGER {
                        vac225(1),
                        vac230(2),
                        vac240(3),
                        vac220(4)
                }
            ACCESS  read-write
            STATUS  mandatory
            DESCRIPTION
                "The UPS's current on-battery output voltage setting
                 (valid for 220/230/240 Vac version UPSs only).  For other
                 version UPSs, reading this object will always return a 0
                 and writing this object will have no effect."
            DEFVAL { vac225 }
            ::= { upsOutputEntry 2 }

        upsOutputPower  OBJECT-TYPE
            SYNTAX  INTEGER
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "The UPS's output load represented as a percentage of full 
                 rated load in Watts.  The value of this object is the actual 
                 percentage * 10 (that is, to determine the actual percentage,
                 divide the value of this object by 10)."
            ::= { upsOutputEntry 3 }


        --==============    upsStatus group          ===================

        --  UPS Status Group
        --  Implementation of this group is mandatory if one or more UPSs
        --  are to be monitored
        --  This group covers information on the Status of each UPS 

        upsStatusTable  OBJECT-TYPE
            SYNTAX  SEQUENCE OF UpsStatusEntry
            ACCESS  not-accessible
            STATUS  mandatory
            DESCRIPTION
                "A list of status table entries.  The number of
                 entries is given by the value of upsNumUPSs."
            ::= { upsStatus 1 }

        upsStatusEntry  OBJECT-TYPE
            SYNTAX  UpsStatusEntry
            ACCESS  not-accessible
            STATUS  mandatory
            DESCRIPTION
                "An entry containing objects for a particular UPS."
            INDEX  { upsIndex }
            ::= { upsStatusTable 1 }

        UpsStatusEntry  ::=
            SEQUENCE {
                upsStatusOperational 
                    INTEGER,
                upsStatusFault
                    INTEGER,
                upsStatusTemp 
                    INTEGER
            }

        upsStatusOperational   OBJECT-TYPE
            SYNTAX  INTEGER         
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "This object contains 8 bits of information about the current
                 operational status of the UPS.  The bits are encoded as
                 follows:

                 BIT 7:  1=replace battery condition
                 BIT 6:  1=low battery condition
                 BIT 5:  1=overloaded output condition
                 BIT 4:  1=on-battery mode of operation
                 BIT 3:  1=on-line mode of operation
                 BIT 2:  1=Smart Boost mode of operation (where applicable)
                 BIT 1:  1=UPS shut down due to low battery, overload,
                           or `sleep' mode
                 BIT 0:  1=run time calibration running

                 Note that bit 0 is the low-order bit."
            ::= { upsStatusEntry 1 }

        upsStatusFault   OBJECT-TYPE
            SYNTAX  INTEGER
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "This object contains 8 bits of information about the current
                 fault conditions of the UPS.  The bits are encoded as
                 follows:

                 BIT 7:  1=UPS fault - internal temperature has exceeded
                           nominal limits
                 BIT 6:  1=UPS fault - bypass relay (where applicable) malfunction
                 BIT 5:  1=UPS fault - battery charger failure
                 BIT 4:  1=UPS in shut down mode via `S' command
                 BIT 3:  1=UPS in `sleep' mode via `@ddd' command
                 BIT 2:  1=UPS fault - main relay malfunction
                 BIT 1:  1=UPS unable to transfer to on-battery operation
                           due to overload
                 BIT 0:  1=UPS's output unpowered due to low battery shut down

                 Note that bit 0 is the low-order bit."
            ::= { upsStatusEntry 2 }

        upsStatusTemp  OBJECT-TYPE
            SYNTAX  INTEGER
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "The UPS's present internal operating temperature in degrees
                 Fahrenheit.  The value of this object is the actual
                 temperature * 10 (that is, to determine the actual
                 temperature, divide the value of this object by 10)."
            ::= { upsStatusEntry 3 }


        --===============    upsConfig group          ====================

        --  UPS Config Group
        --  Implementation of this group is mandatory if one or more UPSs
        --  are to be monitored
        --  This group covers information on the Configuration of each UPS 

        upsConfigTable  OBJECT-TYPE
            SYNTAX  SEQUENCE OF UpsConfigEntry
            ACCESS  not-accessible
            STATUS  mandatory
            DESCRIPTION
                "A list of configuration table entries.  The number of
                 entries is given by the value of upsNumUPSs."
            ::= { upsConfig 1 }

        upsConfigEntry  OBJECT-TYPE
            SYNTAX  UpsConfigEntry
            ACCESS  not-accessible
            STATUS  mandatory
            DESCRIPTION
                "An entry containing objects for a particular UPS."
            INDEX  { upsIndex }
            ::= { upsConfigTable 1 }

        UpsConfigEntry  ::=
            SEQUENCE {
                upsConfigAlarm  
                    INTEGER,
                upsConfigRestoreDefaults  
                    INTEGER
            }

        upsConfigAlarm  OBJECT-TYPE
            SYNTAX  INTEGER {
                        uponUtilityFailure(1),
                        thirtySecondsAfterUtilityFailure(2),
                        lowBatteryOnly(3),
                        noAudibleAlarm(4)
                }
            ACCESS  read-write
            STATUS  mandatory
            DESCRIPTION
                "The UPS's current audible alarm setting.  The alarm
                 may be set to activate immediately upon utility failure
                 and for low battery condition, to activate 30 seconds
                 after utility failure and immediately upon low battery
                 condition, to activate upon low battery condition only,
                 or to not activate under any conditions."
            DEFVAL { uponUtilityFailure }
            ::= { upsConfigEntry 1 }

        upsConfigRestoreDefaults  OBJECT-TYPE
            SYNTAX  INTEGER {
                        restoreDefaults(1)
                }
            ACCESS  read-write
            STATUS  mandatory
            DESCRIPTION
                "This object may be written to force the UPS to restore
                 the factory default settings for most of the UPS's
                 customizable parameters.  Reading this object will always
                 return a 0."
            ::= { upsConfigEntry 2 }



        --===============    upsExtMeas group          ====================

        --  UPS ExtMeas Group
        --  Implementation of this group is mandatory if one or more UPSs
        --  are to be monitored AND an External Measurement Unit is attached
        --  to at least one UPS
        --  This group covers information on the External Measurement Unit of
        --  each UPS 

        upsExtMeasTable  OBJECT-TYPE
            SYNTAX  SEQUENCE OF UpsExtMeasEntry
            ACCESS  not-accessible
            STATUS  mandatory
            DESCRIPTION
                "A list of external measurement table entries.  The number of
                 entries is the number of available UPSs to which External
                 Measurement Units are attached."
            ::= { upsExtMeas 1 }

        upsExtMeasEntry  OBJECT-TYPE
            SYNTAX  UpsExtMeasEntry
            ACCESS  not-accessible
            STATUS  mandatory
            DESCRIPTION
                "An entry containing objects for a particular UPS."
            INDEX  { upsIndex }
            ::= { upsExtMeasTable 1 }

        UpsExtMeasEntry  ::=
            SEQUENCE {
                upsExtMeasFwVersion     
                    DisplayString,
                upsExtMeasTemp  
                    INTEGER,
                upsExtMeasHumidity  
                    INTEGER,
                upsExtMeasAlarmStatus
                    INTEGER,
                upsExtMeasMaxTemp  
                    INTEGER,
                upsExtMeasMinTemp  
                    INTEGER,
                upsExtMeasMaxHumidity  
                    INTEGER,
                upsExtMeasMinHumidity  
                    INTEGER,
                upsExtMeasContact1AlarmControl
                    INTEGER,
                upsExtMeasContact2AlarmControl 
                    INTEGER,
                upsExtMeasContact3AlarmControl  
                    INTEGER,
                upsExtMeasContact4AlarmControl  
                    INTEGER,
                upsExtMeasMaxTempAlarmControl 
                    INTEGER,
                upsExtMeasMinTempAlarmControl
                    INTEGER,
                upsExtMeasMaxHumidityAlarmControl
                    INTEGER,
                upsExtMeasMinHumidityAlarmControl  
                    INTEGER
            }

        upsExtMeasFwVersion     OBJECT-TYPE
            SYNTAX      DisplayString (SIZE(0..1))
            ACCESS      read-only
            STATUS      mandatory
            DESCRIPTION
                "The External Measurement Unit's firmware version letter."
            ::= { upsExtMeasEntry 1 }

        upsExtMeasTemp  OBJECT-TYPE
            SYNTAX  INTEGER
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "The local ambient temperature in degrees Fahrenheit as measured
                 by the External Measurement Unit.  The value of this object
                 is the actual temperature * 100 (that is, to determine the
                 actual temperature, divide the value of this object by 100)."
            ::= { upsExtMeasEntry 2 }

        upsExtMeasHumidity  OBJECT-TYPE
            SYNTAX  INTEGER
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "The local ambient relative humidity in percent as measured
                 by the External Measurement Unit.  The value of this object
                 is the actual humidity * 10 (that is, to determine the
                 actual humidity, divide the value of this object by 10)."
            ::= { upsExtMeasEntry 3 }

        upsExtMeasAlarmStatus  OBJECT-TYPE
            SYNTAX  INTEGER
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "This object contains 8 bits of information about the current
                 alarm status of the External Measurement Unit.  The bits are
                 encoded as follows:

                 BIT 7:  1=Upper temperature limit exceeded
                 BIT 6:  1=Lower temperature limit exceeded
                 BIT 5:  1=Upper relative humidity limit exceeded
                 BIT 4:  1=Lower relative humidity limit exceeded
                 BIT 3:  1=Contact input channel #4 alarm state
                 BIT 2:  1=Contact input channel #3 alarm state
                 BIT 1:  1=Contact input channel #2 alarm state
                 BIT 0:  1=Contact input channel #1 alarm state

                 Note that bit 0 is the low-order bit."
            ::= { upsExtMeasEntry 4 }

        upsExtMeasMaxTemp  OBJECT-TYPE
            SYNTAX  INTEGER {
                        ninetyDegreesF(1),
                        oneHundredFifteenDegreesF(2),
                        oneHundredThirtyDegreesF(3),
                        oneHundredSeventyFiveDegreesF(4)
                }
            ACCESS  read-write
            STATUS  mandatory
            DESCRIPTION
                "The upper temperature limit at which an alarm will be sent."
            DEFVAL { ninetyDegreesF }
            ::= { upsExtMeasEntry 5 }

        upsExtMeasMinTemp  OBJECT-TYPE
            SYNTAX  INTEGER {
                        fortyDegreesF(1),
                        fiftyDegreesF(2),
                        fiftyEightDegreesF(3),
                        sixtyFiveDegreesF(4)
                }
            ACCESS  read-write
            STATUS  mandatory
            DESCRIPTION
                "The lower temperature limit at which an alarm will be sent."
            DEFVAL { fortyDegreesF }
            ::= { upsExtMeasEntry 6 }

        upsExtMeasMaxHumidity  OBJECT-TYPE
            SYNTAX  INTEGER {
                        seventyPercent(1),
                        eightyPercent(2),
                        eightyFivePercent(3),
                        ninetyPercent(4)
                }
            ACCESS  read-write
            STATUS  mandatory
            DESCRIPTION
                "The upper humidity limit at which an alarm will be sent."
            DEFVAL { seventyPercent }
            ::= { upsExtMeasEntry 7 }

        upsExtMeasMinHumidity  OBJECT-TYPE
            SYNTAX  INTEGER {
                        tenPercent(1),
                        twentyPercent(2),
                        thirtyPercent(3),
                        fortyPercent(4)
                }
            ACCESS  read-write
            STATUS  mandatory
            DESCRIPTION
                "The lower humidity limit at which an alarm will be sent."
            DEFVAL { tenPercent }
            ::= { upsExtMeasEntry 8 }

        upsExtMeasContact1AlarmControl  OBJECT-TYPE
            SYNTAX  INTEGER {
                        enable(1),
                        disable(2)
                }
            ACCESS  read-write
            STATUS  mandatory
            DESCRIPTION
                "The alarm enable state for the External Measurement Unit's
                 contact input channel #1.  If enabled, an alarm will be
                 sent when contact input channel #1 has changed to abnormal
                 state."
            ::= { upsExtMeasEntry 9 }
        
        upsExtMeasContact2AlarmControl  OBJECT-TYPE
            SYNTAX  INTEGER {
                        enable(1),
                        disable(2)
                }
            ACCESS  read-write
            STATUS  mandatory
            DESCRIPTION
                "The alarm enable state for the External Measurement Unit's
                 contact input channel #2.  If enabled, an alarm will be
                 sent when contact input channel #2 has changed to abnormal
                 state."
            ::= { upsExtMeasEntry 10 }
        
        upsExtMeasContact3AlarmControl  OBJECT-TYPE
            SYNTAX  INTEGER {
                        enable(1),
                        disable(2)
                }
            ACCESS  read-write
            STATUS  mandatory
            DESCRIPTION
                "The alarm enable state for the External Measurement Unit's
                 contact input channel #3.  If enabled, an alarm will be
                 sent when contact input channel #3 has changed to abnormal
                 state."
            ::= { upsExtMeasEntry 11 }
        
        upsExtMeasContact4AlarmControl  OBJECT-TYPE
            SYNTAX  INTEGER {
                        enable(1),
                        disable(2)
                }
            ACCESS  read-write
            STATUS  mandatory
            DESCRIPTION
                "The alarm enable state for the External Measurement Unit's
                 contact input channel #4.  If enabled, an alarm will be
                 sent when contact input channel #4 has changed to abnormal
                 state."
            ::= { upsExtMeasEntry 12 }

        upsExtMeasMaxTempAlarmControl  OBJECT-TYPE
            SYNTAX  INTEGER {
                        enable(1),
                        disable(2)
                }
            ACCESS  read-write
            STATUS  mandatory
            DESCRIPTION
                "The alarm enable state for the External Measurement Unit's
                 upper temperature limit.  If enabled, an alarm will be
                 sent when the ambient temperature rises above the upper
                 temperature limit."
            ::= { upsExtMeasEntry 13 }
                
        upsExtMeasMinTempAlarmControl  OBJECT-TYPE
            SYNTAX  INTEGER {
                        enable(1),
                        disable(2)
                }
            ACCESS  read-write
            STATUS  mandatory
            DESCRIPTION
                "The alarm enable state for the External Measurement Unit's
                 lower temperature limit.  If enabled, an alarm will be
                 sent when the ambient temperature falls below the lower
                 temperature limit."
            ::= { upsExtMeasEntry 14 }
                
        upsExtMeasMaxHumidityAlarmControl  OBJECT-TYPE
            SYNTAX  INTEGER {
                        enable(1),
                        disable(2)
                }
            ACCESS  read-write
            STATUS  mandatory
            DESCRIPTION
                "The alarm enable state for the External Measurement Unit's
                 upper humidity limit.  If enabled, an alarm will be sent
                 when the ambient relative humidity rises above the upper
                 humidity limit."
            ::= { upsExtMeasEntry 15 }
        
        upsExtMeasMinHumidityAlarmControl  OBJECT-TYPE
            SYNTAX  INTEGER {
                        enable(1),
                        disable(2)
                }
            ACCESS  read-write
            STATUS  mandatory
            DESCRIPTION
                "The alarm enable state for the External Measurement Unit's
                 lower humidity limit.  If enabled, an alarm will be sent
                 when the ambient relative humidity falls below the lower
                 humidity limit."
            ::= { upsExtMeasEntry 16 }
        


        --===============    upsAddlFuncs group          ====================

        --  UPS AddlFuncs Group
        --  Implementation of this group is mandatory if one or more UPSs
        --  are to be monitored AND at least one UPS is capable of supporting
        --  these additional functions
        --  This group covers information on the Additional Functions of each
        --  UPS

        upsAddlFuncsTable  OBJECT-TYPE
            SYNTAX  SEQUENCE OF UpsAddlFuncsEntry
            ACCESS  not-accessible
            STATUS  mandatory
            DESCRIPTION
                "A list of additional functions table entries.  The number of
                 entries is the number of available UPSs which are capable of
                 supporting these additional functions."
            ::= { upsAddlFuncs 1 }

        upsAddlFuncsEntry  OBJECT-TYPE
            SYNTAX  UpsAddlFuncsEntry
            ACCESS  not-accessible
            STATUS  mandatory
            DESCRIPTION
                "An entry containing objects for a particular UPS."
            INDEX  { upsIndex }
            ::= { upsAddlFuncsTable 1 }

        UpsAddlFuncsEntry  ::=
            SEQUENCE {
                upsAddlFuncsNumBatteryPacks 
                    INTEGER,
                upsAddlFuncsNumBadBatteryPacks  
                    INTEGER,
                upsAddlFuncsOutputCurrent 
                    INTEGER,
                upsAddlFuncsOutputApparentPower  
                    INTEGER,
                upsAddlFuncsStatusOperational
                    INTEGER,
                upsAddlFuncsStatusFault
                    INTEGER,
                upsAddlFuncsConfigPassword 
                    OCTET STRING,
                upsAddlFuncsConfigDisable
                    INTEGER,
                upsAddlFuncsConfigBypass 
                    INTEGER
            }

        upsAddlFuncsNumBatteryPacks  OBJECT-TYPE
            SYNTAX  INTEGER
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "The number of battery pack units connected to the UPS."
            ::= { upsAddlFuncsEntry 1 }

        upsAddlFuncsNumBadBatteryPacks  OBJECT-TYPE
            SYNTAX  INTEGER
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "The number of bad (faulty) battery pack units connected 
                 to the UPS."
            ::= { upsAddlFuncsEntry 2 }

        upsAddlFuncsOutputCurrent  OBJECT-TYPE
            SYNTAX  INTEGER
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "The true rms load current drawn from the UPS.  The value
                 of this object is the actual amperage * 100 (that is, to
                 determine the actual amperage, divide the value of this
                 object by 100)."
            ::= { upsAddlFuncsEntry 3 }

        upsAddlFuncsOutputApparentPower  OBJECT-TYPE
            SYNTAX  INTEGER
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "The UPS's output load represented as a percentage of full rated 
                 load in Volt-Amps.  The value of this object is the actual 
                 percentage * 10 (that is, to determine the actual percentage,
                 divide the value of this object by 10)."
            ::= { upsAddlFuncsEntry 4 }

        upsAddlFuncsStatusOperational  OBJECT-TYPE
            SYNTAX  INTEGER         
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "This object contains 8 bits of information about the current
                 operational status of the UPS.  The bits are encoded as
                 follows:

                 BIT 7:  1=UPS ready to power load upon return of normal line
                           or upon user command
                 BIT 6:  1=UPS ready to power load upon user command
                 BIT 5:  1=UPS in bypass mode as a result of manual bypass
                           control
                 BIT 4:  1=UPS is returning from bypass mode
                 BIT 3:  1=UPS in bypass mode as a result of UPS-Link or
                           key command
                 BIT 2:  1=UPS going to bypass mode as a result of UPS-Link
                           or key command
                 BIT 1:  1=not defined
                 BIT 0:  1=wakeup mode - startup test lasting < 2 sec

                 Note that bit 0 is the low-order bit."
            ::= { upsAddlFuncsEntry 5 }

        upsAddlFuncsStatusFault  OBJECT-TYPE
            SYNTAX  INTEGER
            ACCESS  read-only
            STATUS  mandatory
            DESCRIPTION
                "This object contains 8 bits of information about the current
                 fault conditions of the UPS.  The bits are encoded as
                 follows:

                 BIT 7:  reserved for future use
                 BIT 6:  reserved for future use
                 BIT 5:  reserved for future use
                 BIT 4:  1=UPS fault - DC imbalance, UPS in bypass
                 BIT 3:  1=UPS fault - output voltage select failure, UPS
                           in bypass
                 BIT 2:  1=UPS fault - bypass supply failure
                 BIT 1:  1=UPS fault - Isolation Unit fan failure
                 BIT 0:  1=UPS fault - Electronics Unit fan failure, UPS
                           in bypass

                 Note that bit 0 is the low-order bit."
            ::= { upsAddlFuncsEntry 6 }

        upsAddlFuncsConfigPassword  OBJECT-TYPE
            SYNTAX  OCTET STRING
            ACCESS  read-write
            STATUS  mandatory
            DESCRIPTION
                "The password that controls access to the UPS's LCD display.
                 A maximum of 4 characters may be entered."
            ::= { upsAddlFuncsEntry 7 }

        upsAddlFuncsConfigDisable  OBJECT-TYPE
            SYNTAX  INTEGER {
                        disableUps(1)
                }
            ACCESS  read-write
            STATUS  mandatory
            DESCRIPTION
                "This object may be written to immediately shut down the
                 UPS, requiring a manual reset.  Reading this object will
                 always return a 0."
            ::= { upsAddlFuncsEntry 8 }

        upsAddlFuncsConfigBypass  OBJECT-TYPE
            SYNTAX  INTEGER {
                        bypassMode(1),
                        exitBypassMode(2)
                }
            ACCESS  read-write
            STATUS  mandatory
            DESCRIPTION
                "This object may be written to cause the UPS to transfer
                 to or from the bypass mode.  Reading this object will
                 always return a 0."
            ::= { upsAddlFuncsEntry 9 }

END