upsIndex |
.1.3.6.1.4.1.52.4.1.1.10.2.1.1.1 |
A unique value which identifies a particular UPS.
|
upsName |
.1.3.6.1.4.1.52.4.1.1.10.2.1.1.2 |
The UPS's name. A maximum of 8 characters may be specified.
This object is initialized to the UPS's model name.
|
upsModelType |
.1.3.6.1.4.1.52.4.1.1.10.2.1.1.3 |
The UPS's base model type.
|
upsFwVersion |
.1.3.6.1.4.1.52.4.1.1.10.2.1.1.4 |
The UPS's firmware version.
|
upsSerialNumber |
.1.3.6.1.4.1.52.4.1.1.10.2.1.1.5 |
The UPS's serial number as set at the factory.
|
upsManufDate |
.1.3.6.1.4.1.52.4.1.1.10.2.1.1.6 |
The UPS's date of manufacture in the format mm/dd/yy.
|
upsBatteryCapacity |
.1.3.6.1.4.1.52.4.1.1.10.3.1.1.1 |
The UPS's remaining battery capacity expressed as a percent
of the fully charged condition. The value of this object is
the actual percentage * 10 (that is, to determine the actual
percentage, divide the value of this object by 10).
|
upsBatteryVoltage |
.1.3.6.1.4.1.52.4.1.1.10.3.1.1.2 |
The UPS's present battery voltage. The value of this object
is the actual voltage * 100 (that is, to determine the actual
voltage, divide the value of this object by 100).
|
upsBatteryTest |
.1.3.6.1.4.1.52.4.1.1.10.3.1.1.3 |
This object may be written to initiate testing of the UPS's
battery packs. Reading this object will always return a 0.
|
upsBatteryTestResult |
.1.3.6.1.4.1.52.4.1.1.10.3.1.1.4 |
The result of the last battery test performed.
|
upsRunTimeCalibration |
.1.3.6.1.4.1.52.4.1.1.10.3.1.1.5 |
This object may be written to initiate or terminate the test
used to calibrate the returned run time value. This test
will only run if battery capacity is 100%. Results of this
test can be retrieved by upsEstimatedRunTimeRemaining. Valid
values for writing are 1 (initiate test) and 2 (terminate test).
In addition, this object may be read to determine whether
the test is currently running. Valid values for reading
are 3 (test is in progress) and 4 (test is not in progress).
|
upsEstimatedRunTimeRemaining |
.1.3.6.1.4.1.52.4.1.1.10.3.1.1.6 |
The UPS's estimated remaining run time in minutes. The UPS
may be queried when operating in the on-line, bypass, or
on-battery modes of operation. The run time estimate is
based on available battery capacity and output load.
|
upsTransferCause |
.1.3.6.1.4.1.52.4.1.1.10.3.1.1.7 |
The reason for the most recent transfer to on-battery
operation.
|
upsBatteryTestTime |
.1.3.6.1.4.1.52.4.1.1.10.3.1.1.8 |
The frequency of execution of the UPS's automatic battery
test. The test may be run immediately upon startup, upon
startup and every 7 days thereafter, upon startup and every
14 days thereafter, or never.
|
upsLowBatteryWarning |
.1.3.6.1.4.1.52.4.1.1.10.3.1.1.9 |
The interval between activation of the UPS's low battery
alarm warnings and shutdown of the UPS.
|
upsInputUtilityVoltage |
.1.3.6.1.4.1.52.4.1.1.10.4.1.1.1 |
The UPS's utility voltage version.
|
upsInputVoltage |
.1.3.6.1.4.1.52.4.1.1.10.4.1.1.2 |
The UPS's measured utility input voltage. The value
of this object is the actual voltage * 10 (that is, to
determine the actual voltage, divide the value of this
object by 10).
|
upsInputFailureSensitivity |
.1.3.6.1.4.1.52.4.1.1.10.4.1.1.3 |
The sensitivity of the UPS to rapid changes in utility
voltage (e.g., blackouts, spikes, or notches) or
abnormal changes in utility frequency.
|
upsInputMaxVoltage |
.1.3.6.1.4.1.52.4.1.1.10.4.1.1.4 |
The UPS's maximum input voltage recorded since this object
was last read. The value of this object is the actual
voltage * 10 (that is, to determine the actual voltage,
divide the value of this object by 10).
|
upsInputMinVoltage |
.1.3.6.1.4.1.52.4.1.1.10.4.1.1.5 |
The UPS's minimum input voltage recorded since this object
was last read. The value of this object is the actual
voltage * 10 (that is, to determine the actual voltage,
divide the value of this object by 10).
|
upsInputFrequency |
.1.3.6.1.4.1.52.4.1.1.10.4.1.1.6 |
The UPS's present internal operating frequency in Hz.
The value of this object is the actual frequency * 100
(that is, to determine the actual frequency, divide
the value of this object by 100).
|
upsOutputVoltage |
.1.3.6.1.4.1.52.4.1.1.10.5.1.1.1 |
The measured UPS output voltage. The value of this
object is the actual voltage * 10 (that is, to determine
the actual voltage, divide the value of this object by
10).
|
upsOutputUtilityVoltage |
.1.3.6.1.4.1.52.4.1.1.10.5.1.1.2 |
The UPS's current on-battery output voltage setting
(valid for 220/230/240 Vac version UPSs only). For other
version UPSs, reading this object will always return a 0
and writing this object will have no effect.
|
upsOutputPower |
.1.3.6.1.4.1.52.4.1.1.10.5.1.1.3 |
The UPS's output load represented as a percentage of full
rated load in Watts. The value of this object is the actual
percentage * 10 (that is, to determine the actual percentage,
divide the value of this object by 10).
|
upsStatusOperational |
.1.3.6.1.4.1.52.4.1.1.10.6.1.1.1 |
This object contains 8 bits of information about the current
operational status of the UPS. The bits are encoded as
follows:
BIT 7: 1=replace battery condition
BIT 6: 1=low battery condition
BIT 5: 1=overloaded output condition
BIT 4: 1=on-battery mode of operation
BIT 3: 1=on-line mode of operation
BIT 2: 1=Smart Boost mode of operation (where applicable)
BIT 1: 1=UPS shut down due to low battery, overload,
or `sleep' mode
BIT 0: 1=run time calibration running
Note that bit 0 is the low-order bit.
|
upsStatusFault |
.1.3.6.1.4.1.52.4.1.1.10.6.1.1.2 |
This object contains 8 bits of information about the current
fault conditions of the UPS. The bits are encoded as
follows:
BIT 7: 1=UPS fault - internal temperature has exceeded
nominal limits
BIT 6: 1=UPS fault - bypass relay (where applicable) malfunction
BIT 5: 1=UPS fault - battery charger failure
BIT 4: 1=UPS in shut down mode via `S' command
BIT 3: 1=UPS in `sleep' mode via `@ddd' command
BIT 2: 1=UPS fault - main relay malfunction
BIT 1: 1=UPS unable to transfer to on-battery operation
due to overload
BIT 0: 1=UPS's output unpowered due to low battery shut down
Note that bit 0 is the low-order bit.
|
upsStatusTemp |
.1.3.6.1.4.1.52.4.1.1.10.6.1.1.3 |
The UPS's present internal operating temperature in degrees
Fahrenheit. The value of this object is the actual
temperature * 10 (that is, to determine the actual
temperature, divide the value of this object by 10).
|
upsConfigAlarm |
.1.3.6.1.4.1.52.4.1.1.10.7.1.1.1 |
The UPS's current audible alarm setting. The alarm
may be set to activate immediately upon utility failure
and for low battery condition, to activate 30 seconds
after utility failure and immediately upon low battery
condition, to activate upon low battery condition only,
or to not activate under any conditions.
|
upsConfigRestoreDefaults |
.1.3.6.1.4.1.52.4.1.1.10.7.1.1.2 |
This object may be written to force the UPS to restore
the factory default settings for most of the UPS's
customizable parameters. Reading this object will always
return a 0.
|
upsExtMeasFwVersion |
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.1 |
The External Measurement Unit's firmware version letter.
|
upsExtMeasTemp |
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.2 |
The local ambient temperature in degrees Fahrenheit as measured
by the External Measurement Unit. The value of this object
is the actual temperature * 100 (that is, to determine the
actual temperature, divide the value of this object by 100).
|
upsExtMeasHumidity |
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.3 |
The local ambient relative humidity in percent as measured
by the External Measurement Unit. The value of this object
is the actual humidity * 10 (that is, to determine the
actual humidity, divide the value of this object by 10).
|
upsExtMeasAlarmStatus |
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.4 |
This object contains 8 bits of information about the current
alarm status of the External Measurement Unit. The bits are
encoded as follows:
BIT 7: 1=Upper temperature limit exceeded
BIT 6: 1=Lower temperature limit exceeded
BIT 5: 1=Upper relative humidity limit exceeded
BIT 4: 1=Lower relative humidity limit exceeded
BIT 3: 1=Contact input channel #4 alarm state
BIT 2: 1=Contact input channel #3 alarm state
BIT 1: 1=Contact input channel #2 alarm state
BIT 0: 1=Contact input channel #1 alarm state
Note that bit 0 is the low-order bit.
|
upsExtMeasMaxTemp |
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.5 |
The upper temperature limit at which an alarm will be sent.
|
upsExtMeasMinTemp |
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.6 |
The lower temperature limit at which an alarm will be sent.
|
upsExtMeasMaxHumidity |
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.7 |
The upper humidity limit at which an alarm will be sent.
|
upsExtMeasMinHumidity |
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.8 |
The lower humidity limit at which an alarm will be sent.
|
upsExtMeasContact1AlarmControl |
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.9 |
The alarm enable state for the External Measurement Unit's
contact input channel #1. If enabled, an alarm will be
sent when contact input channel #1 has changed to abnormal
state.
|
upsExtMeasContact2AlarmControl |
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.10 |
The alarm enable state for the External Measurement Unit's
contact input channel #2. If enabled, an alarm will be
sent when contact input channel #2 has changed to abnormal
state.
|
upsExtMeasContact3AlarmControl |
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.11 |
The alarm enable state for the External Measurement Unit's
contact input channel #3. If enabled, an alarm will be
sent when contact input channel #3 has changed to abnormal
state.
|
upsExtMeasContact4AlarmControl |
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.12 |
The alarm enable state for the External Measurement Unit's
contact input channel #4. If enabled, an alarm will be
sent when contact input channel #4 has changed to abnormal
state.
|
upsExtMeasMaxTempAlarmControl |
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.13 |
The alarm enable state for the External Measurement Unit's
upper temperature limit. If enabled, an alarm will be
sent when the ambient temperature rises above the upper
temperature limit.
|
upsExtMeasMinTempAlarmControl |
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.14 |
The alarm enable state for the External Measurement Unit's
lower temperature limit. If enabled, an alarm will be
sent when the ambient temperature falls below the lower
temperature limit.
|
upsExtMeasMaxHumidityAlarmControl |
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.15 |
The alarm enable state for the External Measurement Unit's
upper humidity limit. If enabled, an alarm will be sent
when the ambient relative humidity rises above the upper
humidity limit.
|
upsExtMeasMinHumidityAlarmControl |
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.16 |
The alarm enable state for the External Measurement Unit's
lower humidity limit. If enabled, an alarm will be sent
when the ambient relative humidity falls below the lower
humidity limit.
|
upsAddlFuncsNumBatteryPacks |
.1.3.6.1.4.1.52.4.1.1.10.9.1.1.1 |
The number of battery pack units connected to the UPS.
|
upsAddlFuncsNumBadBatteryPacks |
.1.3.6.1.4.1.52.4.1.1.10.9.1.1.2 |
The number of bad (faulty) battery pack units connected
to the UPS.
|
upsAddlFuncsOutputCurrent |
.1.3.6.1.4.1.52.4.1.1.10.9.1.1.3 |
The true rms load current drawn from the UPS. The value
of this object is the actual amperage * 100 (that is, to
determine the actual amperage, divide the value of this
object by 100).
|
upsAddlFuncsOutputApparentPower |
.1.3.6.1.4.1.52.4.1.1.10.9.1.1.4 |
The UPS's output load represented as a percentage of full rated
load in Volt-Amps. The value of this object is the actual
percentage * 10 (that is, to determine the actual percentage,
divide the value of this object by 10).
|
upsAddlFuncsStatusOperational |
.1.3.6.1.4.1.52.4.1.1.10.9.1.1.5 |
This object contains 8 bits of information about the current
operational status of the UPS. The bits are encoded as
follows:
BIT 7: 1=UPS ready to power load upon return of normal line
or upon user command
BIT 6: 1=UPS ready to power load upon user command
BIT 5: 1=UPS in bypass mode as a result of manual bypass
control
BIT 4: 1=UPS is returning from bypass mode
BIT 3: 1=UPS in bypass mode as a result of UPS-Link or
key command
BIT 2: 1=UPS going to bypass mode as a result of UPS-Link
or key command
BIT 1: 1=not defined
BIT 0: 1=wakeup mode - startup test lasting < 2 sec
Note that bit 0 is the low-order bit.
|
upsAddlFuncsStatusFault |
.1.3.6.1.4.1.52.4.1.1.10.9.1.1.6 |
This object contains 8 bits of information about the current
fault conditions of the UPS. The bits are encoded as
follows:
BIT 7: reserved for future use
BIT 6: reserved for future use
BIT 5: reserved for future use
BIT 4: 1=UPS fault - DC imbalance, UPS in bypass
BIT 3: 1=UPS fault - output voltage select failure, UPS
in bypass
BIT 2: 1=UPS fault - bypass supply failure
BIT 1: 1=UPS fault - Isolation Unit fan failure
BIT 0: 1=UPS fault - Electronics Unit fan failure, UPS
in bypass
Note that bit 0 is the low-order bit.
|
upsAddlFuncsConfigPassword |
.1.3.6.1.4.1.52.4.1.1.10.9.1.1.7 |
The password that controls access to the UPS's LCD display.
A maximum of 4 characters may be entered.
|
upsAddlFuncsConfigDisable |
.1.3.6.1.4.1.52.4.1.1.10.9.1.1.8 |
This object may be written to immediately shut down the
UPS, requiring a manual reset. Reading this object will
always return a 0.
|
upsAddlFuncsConfigBypass |
.1.3.6.1.4.1.52.4.1.1.10.9.1.1.9 |
This object may be written to cause the UPS to transfer
to or from the bypass mode. Reading this object will
always return a 0.
|